Parallel-path supply pressure calculator
Parallel-path supply pressure
The worst required parallel path determines the header pressure; losses in separate parallel branches are not added in series.
Units
Pset=max(P1+ΔP1, P2+ΔP2)+ΔPcommon
Pset=max(P1+ΔP1, P2+ΔP2)+ΔPcommon
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- P1 = 80 psig
- ΔP1 = 9 psi
- P2 = 87 psig
- ΔP2 = 4 psi
- ΔPcommon = 6 psi
Pset=max(80+9, 87+4)+6=97
Given
- P1 = 550 kPa gauge
- ΔP1 = 55 kPa
- P2 = 590 kPa gauge
- ΔP2 = 35 kPa
- ΔPcommon = 45 kPa
Pset=max(550+55, 590+35)+45=670
Symbols and units
| Symbol | Meaning | Unit |
| Pset | minimum compressor supply pressure | psig |
| P1 | first end-use minimum pressure | psig |
| ΔP1 | first branch pressure drop | psi |
| P2 | second end-use minimum pressure | psig |
| ΔP2 | second branch pressure drop | psi |
| ΔPcommon | shared treatment pressure drop | psi |
| Symbol | Meaning | Unit |
| Pset | minimum compressor supply pressure | kPa gauge |
| P1 | first end-use minimum pressure | kPa gauge |
| ΔP1 | first branch pressure drop | kPa |
| P2 | second end-use minimum pressure | kPa gauge |
| ΔP2 | second branch pressure drop | kPa |
| ΔPcommon | shared treatment pressure drop | kPa |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.