Avoided exhaust heating cost calculator
Avoided exhaust heating cost
Exhaust reduction saves replacement-air heating in addition to motor electricity.
Units
Sh=ηhV˙×60×Δhday×daysheat×ρ×cp×ΔT×cf
Sh=1000×ηhV˙×Δhday×daysheat×ρ×cp×ΔT×cf
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- V˙ = 6,500 ft³/min
- Δhday = 2.4 h/day
- daysheat = 135 day/yr
- ρ = 0.075 lb/ft³
- cp = 0.24 Btu/(lb·°F)
- ΔT = 31 °F
- cf = 0.000015 $/Btu
- ηh = 0.82 fraction
Sh=0.826500×60×2.4×135×0.075×0.24×31×0.000015≈1,290
Given
- V˙ = 2,800 L/s
- Δhday = 2.5 h/day
- daysheat = 140 day/yr
- ρ = 1.2 kg/m³
- cp = 1.005 kJ/(kg·K)
- ΔT = 20 K
- cf = 0.07 $/kWh
- ηh = 0.85 fraction
Sh=1000×0.852800×2.5×140×1.2×1.005×20×0.07≈1,947
Symbols and units
| Symbol | Meaning | Unit |
| Sh | annual heating savings | $/yr |
| V˙ | avoided equivalent exhaust airflow | ft³/min |
| Δhday | daily exhaust hours avoided | h/day |
| daysheat | annual heating days | day/yr |
| ρ | air density | lb/ft³ |
| cp | air specific heat | Btu/(lb·°F) |
| ΔT | indoor-outdoor temperature difference | °F |
| cf | fuel price | $/Btu |
| ηh | heater efficiency | fraction |
| Symbol | Meaning | Unit |
| Sh | annual heating savings | $/yr |
| V˙ | avoided equivalent exhaust airflow | L/s |
| Δhday | daily exhaust hours avoided | h/day |
| daysheat | annual heating days | day/yr |
| ρ | air density | kg/m³ |
| cp | air specific heat | kJ/(kg·K) |
| ΔT | indoor-outdoor temperature difference | K |
| cf | fuel-energy price per kilowatt-hour | $/kWh |
| ηh | heater efficiency | fraction |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.