Steam required by a coil calculator

Divide the useful heating load by usable enthalpy drop and coil efficiency.

Units
m˙=qwaterηcoil×(hin−hout)\dot{m} = \frac{q_{\text{water}}}{\eta_{\text{coil}} \times \left(h_{\text{in}} - h_{\text{out}}\right)}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

Btu/h
—
Btu/lb
Btu/lb
lb/h

Worked example

Given

  • qwaterq_{\text{water}} = 240,000 Btu/h
  • ηcoil\eta_{\text{coil}} = 0.88 —
  • hinh_{\text{in}} = 1,180 Btu/lb
  • houth_{\text{out}} = 170 Btu/lb
m˙=240,0000.88×(1180−170)≈270\dot{m} = \frac{240{,}000}{0.88 \times \left(1180 - 170\right)} \approx 270

Symbols and units

SymbolMeaningUnit
m˙\dot{m}required steam mass flowlb/h
qwaterq_{\text{water}}useful water-heating rateBtu/h
ηcoil\eta_{\text{coil}}coil heat-transfer efficiency—
hinh_{\text{in}}steam inlet enthalpyBtu/lb
houth_{\text{out}}actual outlet-condensate enthalpyBtu/lb

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.