Steam heat transferred calculator
Steam heat transferred
Multiply steam mass flow by its inlet-to-outlet enthalpy decrease.
Units
q=m˙×(hin−hout)
q=3600m˙×(hin−hout)
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- m˙ = 620 lb/h
- hin = 1,190 Btu/lb
- hout = 180 Btu/lb
q=620×(1190−180)=626,200
Given
- m˙ = 800 kg/h
- hin = 2,800 kJ/kg
- hout = 420 kJ/kg
q=3600800×(2800−420)≈528.9
Symbols and units
| Symbol | Meaning | Unit |
| q | thermal rate delivered | Btu/h |
| m˙ | steam mass flow | lb/h |
| hin | inlet specific enthalpy | Btu/lb |
| hout | outlet specific enthalpy at its actual phase | Btu/lb |
| Symbol | Meaning | Unit |
| q | heat rate delivered | kW |
| m˙ | steam mass flow | kg/h |
| hin | inlet specific enthalpy | kJ/kg |
| hout | outlet specific enthalpy at its actual phase | kJ/kg |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.