Cooling-tower approach calculator
Cooling-tower approach
Tower approach measures how far the leaving water remains above the entering-air wet-bulb temperature.
Units
Approach=Tcold−Twb
Approach=Tcold−Twb
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Tcold = 83 °F
- Twb = 75 °F
Approach=83−75=8
Given
- Tcold = 29 °C
- Twb = 24 °C
Approach=29−24=5
Symbols and units
| Symbol | Meaning | Unit |
| Approach | approach temperature | °F |
| Tcold | leaving tower water temperature | °F |
| Twb | entering-air wet-bulb temperature | °F |
| Symbol | Meaning | Unit |
| Approach | approach temperature | K |
| Tcold | leaving tower water temperature | °C |
| Twb | entering-air wet-bulb temperature | °C |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.