Condenser heat rejection calculator

Condenser heat rejection is calculated as q_cooling + 3412 × P_compressor. Use the stated system boundary and matching input units.

Units
qreject=qcooling+3412×Pcompressorq_{\text{reject}} = q_{\text{cooling}} + 3412 \times P_{\text{compressor}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

Btu/h
kW
Btu/h

Worked example

Given

  • qcoolingq_{\text{cooling}} = 1,200,000 Btu/h
  • PcompressorP_{\text{compressor}} = 70 kW
qreject=1,200,000+3412×70=1,438,840q_{\text{reject}} = 1{,}200{,}000 + 3412 \times 70 = 1{,}438{,}840

Symbols and units

SymbolMeaningUnit
qrejectq_{\text{reject}}condenser heat rejectionBtu/h
qcoolingq_{\text{cooling}}evaporator cooling capacityBtu/h
PcompressorP_{\text{compressor}}compressor electrical inputkW

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.