Air total heat rate calculator
Air total heat rate
Total air heat includes moisture effects through enthalpy; the coefficient assumes standard air density.
Units
qtotal=4.5×CFM×Δh
qtotal=0.0012×Qair×Δh
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- CFM = 6,200 cfm
- Δh = 5.8 Btu/lb
qtotal=4.5×6200×5.8=161,820
Given
- Qair = 2,200 L/s
- Δh = 20 kJ/kg
qtotal=0.0012×2200×20=52.8
Symbols and units
| Symbol | Meaning | Unit |
| qtotal | total air heat rate | Btu/h |
| CFM | air volume flow | cfm |
| Δh | air enthalpy change | Btu/lb |
| Symbol | Meaning | Unit |
| qtotal | total air heat rate | kW |
| Qair | air volume flow | L/s |
| Δh | air enthalpy change | kJ/kg |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.