Required sensible airflow (CFM) calculator
Required sensible airflow
Required standard-air flow is calculated as q_sensible / (1.08 × ΔT). Use the stated system boundary and matching input units.
Units
CFM=1.08×ΔTqsensible
Qair=1.2×ΔT1000×qsensible
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- qsensible = 43,200 Btu/h
- ΔT = 20 °F
CFM=1.08×2043,200=2,000
Given
- qsensible = 42 kW
- ΔT = 10 K
Qair=1.2×101000×42=3,500
Symbols and units
| Symbol | Meaning | Unit |
| CFM | required standard-air flow | cfm |
| qsensible | sensible cooling load | Btu/h |
| ΔT | room-supply dry-bulb difference | °F |
| Symbol | Meaning | Unit |
| Qair | required standard-air flow | L/s |
| qsensible | sensible cooling load | kW |
| ΔT | room-supply dry-bulb difference | K |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.