Fan motor saving at differing efficiency calculator
Fan motor saving at differing efficiency
Electrical savings compare the input needed for each shaft load at its own motor efficiency.
Units
ΔkW=0.746×(ηoldHPold−ηnewHPnew)
ΔkW=ηoldPshaft,old−ηnewPshaft,new
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- HPold = 30 HP
- HPnew = 18 HP
- ηold = 0.9 —
- ηnew = 0.94 —
ΔkW=0.746×(0.930−0.9418)≈10.582
Given
- Pshaft,old = 30 kW
- Pshaft,new = 18 kW
- ηold = 0.9 —
- ηnew = 0.94 —
ΔkW=0.930−0.9418≈14.184
Symbols and units
| Symbol | Meaning | Unit |
| ΔkW | electric input reduction | kW |
| HPold | old actual shaft load | HP |
| HPnew | new actual shaft load | HP |
| ηold | old efficiency | — |
| ηnew | new efficiency | — |
| Symbol | Meaning | Unit |
| ΔkW | electric input reduction | kW |
| Pshaft,old | old actual shaft load | kW |
| Pshaft,new | new actual shaft load | kW |
| ηold | old efficiency | — |
| ηnew | new efficiency | — |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.