ClueLuma

Water heat integrated over two operating intervals calculator

Sum heat-rate products over matching time intervals; multiplying separately averaged flow and temperature difference can bias an audit energy estimate.

Units
E=500×(Q1×ΔT1×h1+Q2×ΔT2×h2)1,000,000E = \frac{500 \times \left(Q_{1} \times {\Delta T_{1}} \times h_{1} + Q_{2} \times {\Delta T_{2}} \times h_{2}\right)}{1{,}000{,}000}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

gpm
°F
h
gpm
°F
h
MMBtu

Worked example

Given

  • Q1Q_{1} = 18 gpm
  • ΔT1{\Delta T_{1}} = 20 °F
  • h1h_{1} = 1.5 h
  • Q2Q_{2} = 8 gpm
  • ΔT2{\Delta T_{2}} = 35 °F
  • h2h_{2} = 2.5 h
E=500×(18×20×1.5+8×35×2.5)1,000,000=0.62E = \frac{500 \times \left(18 \times 20 \times 1.5 + 8 \times 35 \times 2.5\right)}{1{,}000{,}000} = 0.62

Symbols and units

SymbolMeaningUnit
EEwater heat over both measurement intervalsMMBtu
Q1Q_{1}first interval water flowgpm
ΔT1{\Delta T_{1}}first interval water temperature drop°F
h1h_{1}first interval durationh
Q2Q_{2}second interval water flowgpm
ΔT2{\Delta T_{2}}second interval water temperature drop°F
h2h_{2}second interval durationh

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.