ClueLuma

Sensible heat from field airflow calculator

Use measured airflow and temperature difference to estimate sensible heat at standard air conditions.

Units
qair=1.08×Qair×ΔTq_{\text{air}} = 1.08 \times Q_{\text{air}} \times \Delta T

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

cfm
°F
Btu/h

Worked example

Given

  • QairQ_{\text{air}} = 2,200 cfm
  • ΔT\Delta T = 16 °F
qair=1.08×2200×16=38,016q_{\text{air}} = 1.08 \times 2200 \times 16 = 38{,}016

Symbols and units

SymbolMeaningUnit
qairq_{\text{air}}sensible heat rate at standard air conditionsBtu/h
QairQ_{\text{air}}measured air volume flowcfm
ΔT\Delta Tair temperature difference°F

Related calculators