Water heat rate from field readings calculator
Water heat rate from field readings
Use measured water flow and temperature difference for ordinary water; density and heat-capacity changes may require correction.
Units
qwater=500×Qwater×ΔT
qwater=4.19×Qwater×ΔT
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Qwater = 38 gpm
- ΔT = 12 °F
qwater=500×38×12=228,000
Given
- Qwater = 3.5 L/s
- ΔT = 12 K
qwater=4.19×3.5×12≈176
Symbols and units
| Symbol | Meaning | Unit |
| qwater | water heat transfer rate | Btu/h |
| Qwater | measured water volume flow | gpm |
| ΔT | water temperature difference | °F |
| Symbol | Meaning | Unit |
| qwater | water heat transfer rate | kW |
| Qwater | measured water volume flow | L/s |
| ΔT | water temperature difference | K |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.