Ventilation-limited minimum supply fraction calculator

Minimum supply-to-design flow fraction is calculated as V_OA_required / (f_OA × V_design). Use the stated system boundary and matching input units.

Units
fmin=VOA requiredfOA×Vdesignf_{\text{min}} = \frac{V_{\text{OA required}}}{f_{\text{OA}} \times V_{\text{design}}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

cfm
—
cfm
—

Worked example

Given

  • VOA requiredV_{\text{OA required}} = 300 cfm
  • fOAf_{\text{OA}} = 0.25 —
  • VdesignV_{\text{design}} = 2,000 cfm
fmin=3000.25×2000=0.6f_{\text{min}} = \frac{300}{0.25 \times 2000} = 0.6

Symbols and units

SymbolMeaningUnit
fminf_{\text{min}}minimum supply-to-design flow fraction—
VOA requiredV_{\text{OA required}}required delivered outdoor airflowcfm
fOAf_{\text{OA}}constant outdoor fraction within well-mixed supply—
VdesignV_{\text{design}}design maximum supplycfm

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.