Ventilation-limited minimum supply fraction calculator
Ventilation-limited minimum supply fraction
Minimum supply-to-design flow fraction is calculated as V_OA_required / (f_OA × V_design). Use the stated system boundary and matching input units.
Units
fmin=fOA×VdesignVOA required
fmin=fOA×VdesignVOA required
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- VOA required = 300 cfm
- fOA = 0.25 —
- Vdesign = 2,000 cfm
fmin=0.25×2000300=0.6
Given
- VOA required = 150 L/s
- fOA = 0.25 —
- Vdesign = 1,000 L/s
fmin=0.25×1000150=0.6
Symbols and units
| Symbol | Meaning | Unit |
| fmin | minimum supply-to-design flow fraction | — |
| VOA required | required delivered outdoor airflow | cfm |
| fOA | constant outdoor fraction within well-mixed supply | — |
| Vdesign | design maximum supply | cfm |
| Symbol | Meaning | Unit |
| fmin | minimum supply-to-design flow fraction | — |
| VOA required | required delivered outdoor airflow | L/s |
| fOA | constant outdoor fraction within well-mixed supply | — |
| Vdesign | design maximum supply | L/s |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.