Outdoor fraction from mixed-air temperatures calculator
Outdoor fraction from mixed-air temperatures
Outdoor fraction of mixed airflow is calculated as (T_mix−T_return)/(T_outdoor−T_return). Use the stated system boundary and matching input units.
Units
fOA=Toutdoor−TreturnTmix−Treturn
fOA=Toutdoor−TreturnTmix−Treturn
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Tmix = 61 °F
- Treturn = 75 °F
- Toutdoor = 40 °F
fOA=40−7561−75=0.4
Given
- Tmix = 16 °C
- Treturn = 24 °C
- Toutdoor = 4 °C
fOA=4−2416−24=0.4
Symbols and units
| Symbol | Meaning | Unit |
| fOA | outdoor fraction of mixed airflow | — |
| Tmix | well-mixed supply-box dry bulb | °F |
| Treturn | return-air dry bulb | °F |
| Toutdoor | outdoor-air dry bulb | °F |
| Symbol | Meaning | Unit |
| fOA | outdoor fraction of mixed airflow | — |
| Tmix | well-mixed supply-box dry bulb | °C |
| Treturn | return-air dry bulb | °C |
| Toutdoor | outdoor-air dry bulb | °C |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.