Opaque-wall resistance within a shared heat limit calculator

Minimum opaque-wall heat resistance is calculated as A_wall × ΔT / (q_limit − U_glass × A_glass × ΔT). Use the stated system boundary and matching input units.

Units
Rwall=Awall×ΔTqlimit−Uglass×Aglass×ΔTR_{\text{wall}} = \frac{A_{\text{wall}} \times \Delta T}{q_{\text{limit}} - U_{\text{glass}} \times A_{\text{glass}} \times \Delta T}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

ft²
°F
Btu/h
Btu/(h·ft²·°F)
ft²
h·ft²·°F/Btu

Worked example

Given

  • AwallA_{\text{wall}} = 8,000 ft²
  • ΔT\Delta T = 40 °F
  • qlimitq_{\text{limit}} = 100,000 Btu/h
  • UglassU_{\text{glass}} = 0.5 Btu/(h·ft²·°F)
  • AglassA_{\text{glass}} = 2,000 ft²
Rwall=8000×40100,000−0.5×2000×40≈5.333R_{\text{wall}} = \frac{8000 \times 40}{100{,}000 - 0.5 \times 2000 \times 40} \approx 5.333

Symbols and units

SymbolMeaningUnit
RwallR_{\text{wall}}minimum opaque-wall heat resistanceh·ft²·°F/Btu
AwallA_{\text{wall}}opaque wall areaft²
ΔT\Delta Tinside-outside temperature difference°F
qlimitq_{\text{limit}}maximum shared conductive heat lossBtu/h
UglassU_{\text{glass}}glazing conductanceBtu/(h·ft²·°F)
AglassA_{\text{glass}}glazing areaft²

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.