Two-period discharge requirement calculator

Integrate only positive load deficits when event charging is unavailable; spare chiller capacity during a lower-load interval cannot reduce prior required discharge.

Units
C=max⁡(L1−Q, 0)×t1+max⁡(L2−Q, 0)×t2C = \max\left(L_{1} - Q,\ 0\right) \times t_{1} + \max\left(L_{2} - Q,\ 0\right) \times t_{2}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

ton
ton
h
ton
h
ton·h

Worked example

Given

  • L1L_{1} = 310 ton
  • QQ = 230 ton
  • t1t_{1} = 4 h
  • L2L_{2} = 170 ton
  • t2t_{2} = 2 h
C=max⁡(310−230, 0)×4+max⁡(170−230, 0)×2=320C = \max\left(310 - 230,\ 0\right) \times 4 + \max\left(170 - 230,\ 0\right) \times 2 = 320

Symbols and units

SymbolMeaningUnit
CCrequired discharged cooling energyton·h
L1L_{1}first cooling loadton
QQchiller capacity assigned to the loadton
t1t_{1}first durationh
L2L_{2}second cooling loadton
t2t_{2}second durationh