Available thermal charging output calculator
Available thermal charging output
Only production left after simultaneous cooling loads can charge the tank.
Units
Qcharge=max(Qchiller−Llive, 0)
Qcharge=max(Qchiller−Llive, 0)
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Qchiller = 220 ton
- Llive = 70 ton
Qcharge=max(220−70, 0)=150
Given
- Qchiller = 800 kW
- Llive = 260 kW
Qcharge=max(800−260, 0)=540
Symbols and units
| Symbol | Meaning | Unit |
| Qcharge | output available to charge storage | ton |
| Qchiller | chiller output during charging | ton |
| Llive | simultaneous live cooling load | ton |
| Symbol | Meaning | Unit |
| Qcharge | output available to charge storage | kW |
| Qchiller | chiller output during charging | kW |
| Llive | simultaneous live cooling load | kW |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.