Required peak thermal storage calculator

Required storage discharge energy is calculated as (Load_tons − Operating_chiller_tons) × Duration. Use the stated system boundary and matching input units.

Units
Storage=(Loadtons−Operating chiller tons)×Duration\text{Storage} = \left(\text{Load}_{\text{tons}} - \text{Operating chiller tons}\right) \times \text{Duration}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

ton
ton
h
ton-hour

Worked example

Given

  • Loadtons\text{Load}_{\text{tons}} = 400 ton
  • Operating chiller tons\text{Operating chiller tons} = 250 ton
  • Duration\text{Duration} = 4 h
Storage=(400−250)×4=600\text{Storage} = \left(400 - 250\right) \times 4 = 600

Symbols and units

SymbolMeaningUnit
Storage\text{Storage}required storage discharge energyton-hour
Loadtons\text{Load}_{\text{tons}}constant cooling load during dischargeton
Operating chiller tons\text{Operating chiller tons}concurrent operating chiller capacityton
Duration\text{Duration}discharge periodh

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.