Required chilled-water tank volume calculator
Required chilled-water tank volume
Convert delivered ton-hours to water volume after allowing for useful temperature range and capacity losses.
Units
V=8.34×dT×u12,000×C×100
V=4.19×dT×u3600×C×100
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- C = 800 ton·h
- dT = 18 Δ°F
- u = 90 %
V=8.34×18×9012,000×800×100≈71,054
Given
- C = 2,500 kWh
- dT = 9 K
- u = 90 %
V=4.19×9×903600×2500×100≈265,182
Symbols and units
| Symbol | Meaning | Unit |
| V | required tank water volume | gal |
| C | delivered cooling energy | ton·h |
| dT | temperature difference | Δ°F |
| u | usable-capacity factor | % |
| Symbol | Meaning | Unit |
| V | required tank water volume | L |
| C | delivered cooling energy | kWh |
| dT | temperature difference | K |
| u | usable-capacity factor | % |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.