Required chilled-water tank volume calculator

Convert delivered ton-hours to water volume after allowing for useful temperature range and capacity losses.

Units
V=12,000×C×1008.34×dT×uV = \frac{12{,}000 \times C \times 100}{8.34 \times \mathit{dT} \times u}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

ton·h
Δ°F
%
gal

Worked example

Given

  • CC = 800 ton·h
  • dT\mathit{dT} = 18 Δ°F
  • uu = 90 %
V=12,000×800×1008.34×18×90≈71,054V = \frac{12{,}000 \times 800 \times 100}{8.34 \times 18 \times 90} \approx 71{,}054

Symbols and units

SymbolMeaningUnit
VVrequired tank water volumegal
CCdelivered cooling energyton·h
dT\mathit{dT}temperature differenceΔ°F
uuusable-capacity factor%

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.