Reactive compensation for a feeder-current limit calculator

Minimum reactive compensation is calculated as Q_old − sqrt([sqrt(3) × V_LL × I_limit/1000]² − P²). Use the stated system boundary and matching input units.

QC,min=Qold−(3×VLL×Ilimit1000)2−P2Q_{\text{C,min}} = Q_{\text{old}} - \sqrt{\left(\frac{\sqrt{3} \times V_{\text{LL}} \times I_{\text{limit}}}{1000}\right)^{2} - P^{2}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

kW
kVAR
V
A
kVAR

Worked example

Given

  • PP = 50 kW
  • QoldQ_{\text{old}} = 150 kVAR
  • VLLV_{\text{LL}} = 480 V
  • IlimitI_{\text{limit}} = 150 A
QC,min=150−(3×480×1501000)2−502≈35.755Q_{\text{C,min}} = 150 - \sqrt{\left(\frac{\sqrt{3} \times 480 \times 150}{1000}\right)^{2} - {50}^{2}} \approx 35.755

Symbols and units

SymbolMeaningUnit
QC,minQ_{\text{C,min}}minimum reactive compensationkVAR
PPunchanged feeder real loadkW
QoldQ_{\text{old}}initial inductive reactive requirementkVAR
VLLV_{\text{LL}}line-to-line voltageV
IlimitI_{\text{limit}}maximum allowed line currentA