Line voltage from balanced real power calculator

Required line-to-line voltage is calculated as 1000 × P / (sqrt(3) × I × PF). Use the stated system boundary and matching input units.

VLL=1000×P3×I×PFV_{\text{LL}} = \frac{1000 \times P}{\sqrt{3} \times I \times \mathrm{PF}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

kW
A
—
V

Worked example

Given

  • PP = 100 kW
  • II = 50 A
  • PF\mathrm{PF} = 0.8 —
VLL=1000×1003×50×0.8≈1,443V_{\text{LL}} = \frac{1000 \times 100}{\sqrt{3} \times 50 \times 0.8} \approx 1{,}443

Symbols and units

SymbolMeaningUnit
VLLV_{\text{LL}}required line-to-line voltageV
PPbalanced real input powerkW
IIline currentA
PF\mathrm{PF}combined power factor—

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.