Additional reactive compensation calculator

Additional capacitor capacity is the reactive compensation needed to reach the target power factor at unchanged real load, less the capacitor capacity already operating.

Qadd=P×(1−PF12PF1−1−PF22PF2)−QexistingQ_{\text{add}} = P \times \left(\frac{\sqrt{1 - \mathrm{PF}_{1}^{2}}}{\mathrm{PF}_{1}} - \frac{\sqrt{1 - \mathrm{PF}_{2}^{2}}}{\mathrm{PF}_{2}}\right) - Q_{\text{existing}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

kW
—
—
kVAR
kVAR

Worked example

Given

  • PP = 500 kW
  • PF1\mathrm{PF}_{1} = 0.75 —
  • PF2\mathrm{PF}_{2} = 0.95 —
  • QexistingQ_{\text{existing}} = 100 kVAR
Qadd=500×(1−0.7520.75−1−0.9520.95)−100≈176.6Q_{\text{add}} = 500 \times \left(\frac{\sqrt{1 - {0.75}^{2}}}{0.75} - \frac{\sqrt{1 - {0.95}^{2}}}{0.95}\right) - 100 \approx 176.6

Symbols and units

SymbolMeaningUnit
QaddQ_{\text{add}}additional capacitor capacitykVAR
PPunchanged real loadkW
PF1\mathrm{PF}_{1}initial uncorrected power factor—
PF2\mathrm{PF}_{2}target power factor—
QexistingQ_{\text{existing}}operating existing capacitor capacitykVAR