Pump excess electrical input calculator

Compare metered input with the accepted clean electrical input at the same required hydraulic duty. Wire-to-water efficiency already includes pump and motor losses.

Units
Pexcess=Pmeter−0.746×Q×H3960×ηcleanP_{\text{excess}} = P_{\text{meter}} - \frac{0.746 \times Q \times H}{3960 \times \eta_{\text{clean}}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

kW
gpm
ft
fraction
kW

Worked example

Given

  • PmeterP_{\text{meter}} = 18 kW
  • QQ = 500 gpm
  • HH = 95 ft
  • ηclean\eta_{\text{clean}} = 0.72 fraction
Pexcess=18−0.746×500×953960×0.72≈5.572P_{\text{excess}} = 18 - \frac{0.746 \times 500 \times 95}{3960 \times 0.72} \approx 5.572

Symbols and units

SymbolMeaningUnit
PexcessP_{\text{excess}}excess input above accepted clean dutykW
PmeterP_{\text{meter}}measured electrical inputkW
QQrequired water flowgpm
HHrequired water headft
ηclean\eta_{\text{clean}}accepted clean wire-to-water efficiencyfraction