Heat-transfer restoration ratio calculator

Use Q = UA × LMTD under the same exchanger geometry and comparable flow regime. Raw heat duty alone cannot establish cleaning effectiveness when the driving temperature difference changes.

Units
UArel=Qafter×ΔTlm,cleanΔTlm,after×Qclean\mathrm{UA}_{\text{rel}} = \frac{Q_{\text{after}} \times {\Delta T_{\text{lm,clean}}}}{{\Delta T_{\text{lm,after}}} \times Q_{\text{clean}}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

Btu/h
°F
Btu/h
°F
ratio

Worked example

Given

  • QafterQ_{\text{after}} = 400,000 Btu/h
  • ΔTlm,after{\Delta T_{\text{lm,after}}} = 20 °F
  • QcleanQ_{\text{clean}} = 550,000 Btu/h
  • ΔTlm,clean{\Delta T_{\text{lm,clean}}} = 25 °F
UArel=400,000×2520×550,000≈0.9091\mathrm{UA}_{\text{rel}} = \frac{400{,}000 \times 25}{20 \times 550{,}000} \approx 0.9091

Symbols and units

SymbolMeaningUnit
UArel\mathrm{UA}_{\text{rel}}restored-to-clean heat-transfer conductanceratio
QafterQ_{\text{after}}heat duty after maintenanceBtu/h
ΔTlm,after{\Delta T_{\text{lm,after}}}post-maintenance log-mean temperature difference°F
QcleanQ_{\text{clean}}clean-reference heat dutyBtu/h
ΔTlm,clean{\Delta T_{\text{lm,clean}}}clean-reference log-mean temperature difference°F