Isothermal receiver free-air rate calculator

This ideal isothermal drawdown balance estimates average free-air use, without a leakage-pressure correction.

Units
Qfree=V×(P1−P2)Patm×tQ_{\text{free}} = \frac{V \times \left(P_{1} - P_{2}\right)}{P_{\text{atm}} \times t}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

ft³
psig
psig
psia
min
cfm

Worked example

Given

  • VV = 120 ft³
  • P1P_{1} = 105 psig
  • P2P_{2} = 85 psig
  • PatmP_{\text{atm}} = 14.7 psia
  • tt = 2 min
Qfree=120×(105−85)14.7×2≈81.633Q_{\text{free}} = \frac{120 \times \left(105 - 85\right)}{14.7 \times 2} \approx 81.633

Symbols and units

SymbolMeaningUnit
QfreeQ_{\text{free}}average free-air withdrawalcfm
VVconnected tank and piping volumeft³
P1P_{1}initial gauge pressurepsig
P2P_{2}final gauge pressurepsig
PatmP_{\text{atm}}site atmospheric pressurepsia
ttwithdrawal durationmin