Process refrigeration COP calculator
Process refrigeration COP
Convert cooling output to the same energy-rate units as electrical input before forming the ratio.
Units
COP=3412×P12,000×Qton
COP=PQcooling
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Qton = 150 ton
- P = 120 kW
COP=3412×12012,000×150≈4.396
Given
- Qcooling = 600 kW
- P = 150 kW
COP=150600=4
Symbols and units
| Symbol | Meaning | Unit |
| COP | coefficient of performance | ratio |
| Qton | useful cooling output | ton |
| P | electrical input on stated boundary | kW |
| Symbol | Meaning | Unit |
| COP | coefficient of performance | ratio |
| Qcooling | useful cooling output | kW |
| P | electrical input on stated boundary | kW |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.