Economizer electric-energy savings calculator

The example converts avoided cooling load to electric input using COP and 3412 Btu/kWh.

Units
ΔE=H×V˙×60×ρCOP×3412\Delta E = \frac{H \times \dot{V} \times 60 \times \rho}{\mathrm{COP} \times 3412}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

Btu·h/(lb·yr)
ft³/min
lb/ft³
ratio
kWh/yr

Worked example

Given

  • HH = 8,600 Btu·h/(lb·yr)
  • V˙\dot{V} = 9,800 ft³/min
  • ρ\rho = 0.075 lb/ft³
  • COP\mathrm{COP} = 3.4 ratio
ΔE=8600×9800×60×0.0753.4×3412≈32,693\Delta E = \frac{8600 \times 9800 \times 60 \times 0.075}{3.4 \times 3412} \approx 32{,}693

Symbols and units

SymbolMeaningUnit
ΔE\Delta Eavoided electricitykWh/yr
HHintegrated favorable enthalpy differenceBtu·h/(lb·yr)
V˙\dot{V}airflowft³/min
ρ\rhoair densitylb/ft³
COP\mathrm{COP}air-conditioner performanceratio

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.