Annual compressor-air heat recovery calculator
Annual compressor-air heat recovery
Recovery only counts while rejected heat and useful heating demand coincide.
Units
Qrec=V˙×ρ×cp×ΔT×60×h×LF
Qrec=1000V˙×ρ×cp×ΔT×h×LF
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- V˙ = 3,600 ft³/min
- ρ = 0.075 lb/ft³
- cp = 0.24 Btu/(lb·°F)
- ΔT = 38 °F
- h = 1,700 h/yr
- LF = 0.78 fraction
Qrec=3600×0.075×0.24×38×60×1700×0.78=195,908,544
Given
- V˙ = 1,000 L/s
- ρ = 1.2 kg/m³
- cp = 1.005 kJ/(kg·K)
- ΔT = 40 K
- h = 3,800 h/yr
- LF = 0.75 fraction
Qrec=10001000×1.2×1.005×40×3800×0.75=137,484
Symbols and units
| Symbol | Meaning | Unit |
| Qrec | annual recovered air heat | Btu/yr |
| V˙ | cooling-air flow | ft³/min |
| ρ | cooling-air density | lb/ft³ |
| cp | air specific heat | Btu/(lb·°F) |
| ΔT | cooling-air temperature rise | °F |
| h | hours with useful heating demand | h/yr |
| LF | applicable load fraction | fraction |
| Symbol | Meaning | Unit |
| Qrec | annual recovered air heat | kWh/year |
| V˙ | cooling-air flow | L/s |
| ρ | cooling-air density | kg/m³ |
| cp | air specific heat | kJ/(kg·K) |
| ΔT | cooling-air temperature rise | K |
| h | hours with useful heating demand | h/yr |
| LF | applicable load fraction | fraction |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.