Convection-loss estimate calculator
Convection-loss estimate
An empirical heat-loss estimator in the specified US units.
Units
qconv=A×0.18×(Ts−Troom)4/3
qconv=A×0.00124330840649×(Ts−Troom)4/3
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Troom = 70 °F
- Ts = 150 °F
- A = 100 ft²
qconv=100×0.18×(150−70)4/3≈6,205
Given
- Troom = 25 °C
- Ts = 150 °C
- A = 12 m²
qconv=12×0.00124330840649×(150−25)4/3≈9.325
Symbols and units
| Symbol | Meaning | Unit |
| qconv | convective heat loss | Btu/h |
| Troom | ambient temperature | °F |
| Ts | surface temperature | °F |
| A | exposed surface area | ft² |
| Symbol | Meaning | Unit |
| qconv | convective heat loss | kW |
| Troom | ambient temperature | °C |
| Ts | surface temperature | °C |
| A | exposed surface area | m² |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.