Ideal load-leveling chiller size calculator
Ideal load-leveling chiller size
An ideal lossless load-leveling plant produces daily cooling at a steady rate across its running hours.
Units
Qlevel=trunCday
Qlevel=trunCday
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Cday = 4,200 ton·h/day
- trun = 24 h/day
Qlevel=244200=175
Given
- Cday = 16,000 kWh/day
- trun = 20 h/day
Qlevel=2016,000=800
Symbols and units
| Symbol | Meaning | Unit |
| Qlevel | constant chiller output | ton |
| Cday | total daily cooling | ton·h/day |
| trun | available daily running time | h/day |
| Symbol | Meaning | Unit |
| Qlevel | constant chiller output | kW |
| Cday | total daily cooling | kWh/day |
| trun | available daily running time | h/day |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.