Required lumen-method fixture count calculator
Required lumen-method fixture count
Calculated fixture count is calculated as E × A / (L × CU × LLF). Use the stated system boundary and matching input units.
Units
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- = 50 fc
- = 2,400 ft²
- = 5,000 lm
- = 0.65 —
- = 0.75 —
Given
- = 500 lux
- = 256 m²
- = 5,000 lm
- = 0.64 —
- = 0.8 —
Symbols and units
| Symbol | Meaning | Unit |
|---|---|---|
| calculated fixture count | fixture | |
| maintained target illuminance | fc | |
| task-plane area | ft² | |
| initial lumens per fixture | lm | |
| coefficient of utilization | — | |
| light-loss factor | — |
| Symbol | Meaning | Unit |
|---|---|---|
| calculated fixture count | fixture | |
| maintained target illuminance | lux | |
| task-plane area | m² | |
| initial lumens per fixture | lm | |
| coefficient of utilization | — | |
| light-loss factor | — |
Related calculators
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.