Maintained average illuminance calculator

The lumen method estimates maintained average work-plane illuminance from fixture output, utilization and losses.

Units
Efc=N×L×CU×LLFAE_{\text{fc}} = \frac{N \times L \times \mathrm{CU} \times \mathrm{LLF}}{A}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

—
lm
—
—
ft²
fc

Worked example

Given

  • NN = 36 —
  • LL = 5,200 lm
  • CU\mathrm{CU} = 0.64 —
  • LLF\mathrm{LLF} = 0.8 —
  • AA = 2,800 ft²
Efc=36×5200×0.64×0.82800≈34.231E_{\text{fc}} = \frac{36 \times 5200 \times 0.64 \times 0.8}{2800} \approx 34.231

Symbols and units

SymbolMeaningUnit
EfcE_{\text{fc}}maintained illuminancefc
NNnumber of luminaires—
LLinitial lumens per luminairelm
CU\mathrm{CU}utilization coefficient—
LLF\mathrm{LLF}combined light-loss factor—
AAwork-plane areaft²