Limited outdoor-temperature reset calculator
Limited outdoor-temperature reset
Linear outdoor reset is limited by the minimum water temperature needed for equipment or service.
Units
Tcmd=max(Tmin, Tsc+Tow−Toc(To−Toc)×(Tsw−Tsc))
Tcmd=max(Tmin, Tsc+Tow−Toc(To−Toc)×(Tsw−Tsc))
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- Tmin = 145 °F
- To = 42 °F
- Toc = 15 °F
- Tsc = 185 °F
- Tow = 65 °F
- Tsw = 125 °F
Tcmd=max(145, 185+65−15(42−15)×(125−185))=152.6
Given
- Tmin = 60 °C
- To = 10 °C
- Toc = -5 °C
- Tsc = 85 °C
- Tow = 20 °C
- Tsw = 55 °C
Tcmd=max(60, 85+20−(−5)[10−(−5)]×(55−85))=67
Symbols and units
| Symbol | Meaning | Unit |
| Tcmd | requested supply temperature | °F |
| Tmin | minimum permitted supply temperature | °F |
| To | outdoor temperature | °F |
| Toc | cold outdoor anchor | °F |
| Tsc | supply temperature at cold anchor | °F |
| Tow | warm outdoor anchor | °F |
| Tsw | supply temperature at warm anchor | °F |
| Symbol | Meaning | Unit |
| Tcmd | requested supply temperature | °C |
| Tmin | minimum permitted supply temperature | °C |
| To | outdoor temperature | °C |
| Toc | cold outdoor anchor | °C |
| Tsc | supply temperature at cold anchor | °C |
| Tow | warm outdoor anchor | °C |
| Tsw | supply temperature at warm anchor | °C |