Equal-load chiller staging crossover calculator

Compare one machine carrying all load with two identical machines sharing it equally, within the observed curve range. The second fixed input is offset by smaller combined quadratic loading.

Units
Lcross=2×baL_{\text{cross}} = \sqrt{\frac{2 \times b}{a}}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

kW
kW/ton²
ton

Worked example

Given

  • bb = 22 kW
  • aa = 0.00055 kW/ton²
Lcross=2×220.00055≈282.8L_{\text{cross}} = \sqrt{\frac{2 \times 22}{0.00055}} \approx 282.8

Symbols and units

SymbolMeaningUnit
LcrossL_{\text{cross}}total cooling load at equal inputton
bbfixed input of each operating chillerkW
aaquadratic part-load coefficientkW/ton²

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.