Cooling-tower evaporation rule calculator

Approximation: for each 10 Δ°F cooling range, about 1% of circulation evaporates in the reference rule.

Units
V˙evap=V˙circulating×0.01×ΔT10\dot{V}_{\text{evap}} = \frac{\dot{V}_{\text{circulating}} \times 0.01 \times \Delta T}{10}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

gpm
°F
gpm

Worked example

Given

  • V˙circulating\dot{V}_{\text{circulating}} = 2,400 gpm
  • ΔT\Delta T = 12 °F
V˙evap=2400×0.01×1210=28.8\dot{V}_{\text{evap}} = \frac{2400 \times 0.01 \times 12}{10} = 28.8

Symbols and units

SymbolMeaningUnit
V˙evap\dot{V}_{\text{evap}}evaporation flowgpm
V˙circulating\dot{V}_{\text{circulating}}circulating-water flowgpm
ΔT\Delta Ttower water temperature drop°F