Liquid-water sensible heat calculator
Liquid-water sensible heat
Uses 8.34 lb/1 gal water density and Cp near 1 Btu/(1 lb·1 Δ°F).Uses 3.78 kg/3.79 L water density and Cp near 1.06 kJ/(0.454 kg·0.556 Δ°C).
Units
qwater=500×GPM×ΔT
qwater=4.19×Qwater×ΔT
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- GPM = 100 gal/min
- ΔT = 10 °F
qwater=500×100×10=500,000
Given
- Qwater = 8 L/s
- ΔT = 30 K
qwater=4.19×8×30≈1,006
Symbols and units
| Symbol | Meaning | Unit |
| qwater | water sensible heat rate | Btu/h |
| GPM | liquid-water flow | gal/min |
| ΔT | water temperature change | °F |
| Symbol | Meaning | Unit |
| qwater | water sensible heat rate | kW |
| Qwater | liquid-water flow | L/s |
| ΔT | water temperature change | K |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.