General motor power savings calculator
General motor power savings
Subtract electrical inputs while preserving required mechanical service.
Units
ΔkW=0.746×(ηoldHPold×LFold−ηnewHPnew×LFnew)
ΔkW=ηoldPrated,old×LFold−ηnewPrated,new×LFnew
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- HPold = 100 HP
- LFold = 0.6 —
- HPnew = 75 HP
- LFnew = 0.75 —
- ηold = 0.88 —
- ηnew = 0.945 —
ΔkW=0.746×(0.88100×0.6−0.94575×0.75)≈6.459
Given
- Prated,old = 75 kW
- LFold = 0.6 —
- Prated,new = 55 kW
- LFnew = 0.65 —
- ηold = 0.88 —
- ηnew = 0.94 —
ΔkW=0.8875×0.6−0.9455×0.65≈13.104
Symbols and units
| Symbol | Meaning | Unit |
| ΔkW | electrical input reduction | kW |
| HPold | old rated shaft horsepower | HP |
| LFold | old load fraction | — |
| HPnew | new rated shaft horsepower | HP |
| LFnew | new load fraction | — |
| ηold | old efficiency | — |
| ηnew | new efficiency | — |
| Symbol | Meaning | Unit |
| ΔkW | electrical input reduction | kW |
| Prated,old | old rated shaft power | kW |
| LFold | old load fraction | — |
| Prated,new | new rated shaft power | kW |
| LFnew | new load fraction | — |
| ηold | old efficiency | — |
| ηnew | new efficiency | — |
Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.