General motor power savings calculator

Subtract electrical inputs while preserving required mechanical service.

Units
ΔkW=0.746×(HPold×LFoldηold−HPnew×LFnewηnew)\Delta \mathrm{kW} = 0.746 \times \left(\frac{\mathrm{HP}_{\text{old}} \times \mathrm{LF}_{\text{old}}}{\eta_{\text{old}}} - \frac{\mathrm{HP}_{\text{new}} \times \mathrm{LF}_{\text{new}}}{\eta_{\text{new}}}\right)

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

HP
—
HP
—
—
—
kW

Worked example

Given

  • HPold\mathrm{HP}_{\text{old}} = 100 HP
  • LFold\mathrm{LF}_{\text{old}} = 0.6 —
  • HPnew\mathrm{HP}_{\text{new}} = 75 HP
  • LFnew\mathrm{LF}_{\text{new}} = 0.75 —
  • ηold\eta_{\text{old}} = 0.88 —
  • ηnew\eta_{\text{new}} = 0.945 —
ΔkW=0.746×(100×0.60.88−75×0.750.945)≈6.459\Delta \mathrm{kW} = 0.746 \times \left(\frac{100 \times 0.6}{0.88} - \frac{75 \times 0.75}{0.945}\right) \approx 6.459

Symbols and units

SymbolMeaningUnit
ΔkW\Delta \mathrm{kW}electrical input reductionkW
HPold\mathrm{HP}_{\text{old}}old rated shaft horsepowerHP
LFold\mathrm{LF}_{\text{old}}old load fraction—
HPnew\mathrm{HP}_{\text{new}}new rated shaft horsepowerHP
LFnew\mathrm{LF}_{\text{new}}new load fraction—
ηold\eta_{\text{old}}old efficiency—
ηnew\eta_{\text{new}}new efficiency—

Related calculators

Results are estimates for study and screening. Check the inputs, units and assumptions before you use them for design, billing or contract decisions.