ClueLuma

Breathing-zone outdoor air calculator

Combines person-based and floor-area-based outdoor air requirements.

Units
Vbz=Rp×Pz+Ra×AzV_{\text{bz}} = R_{p} \times P_{z} + R_{a} \times A_{z}

Calculator

Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.

cfm/person
person
cfm/ft²
ft²
cfm

Worked example

Given

  • RpR_{p} = 5 cfm/person
  • PzP_{z} = 25 person
  • RaR_{a} = 0.06 cfm/ft²
  • AzA_{z} = 1,000 ft²
Vbz=5×25+0.06×1000=185V_{\text{bz}} = 5 \times 25 + 0.06 \times 1000 = 185

Symbols and units

SymbolMeaningUnit
VbzV_{\text{bz}}breathing-zone outdoor airflowcfm
RpR_{p}people outdoor-air ratecfm/person
PzP_{z}zone populationperson
RaR_{a}area outdoor-air ratecfm/ft²
AzA_{z}zone floor areaft²

Related calculators