Balanced three-phase line current calculator
Balanced three-phase line current
Line current is calculated as 1000 × P/(sqrt(3) × V_LL × PF). Use the stated system boundary and matching input units.
Calculator
Enter the values you know and leave one box empty. Calculate finds the empty one, the result or any input.
Worked example
Given
- = 200 kW
- = 480 V
- = 0.85 —
Symbols and units
| Symbol | Meaning | Unit |
|---|---|---|
| line current | A | |
| real power | kW | |
| line voltage | V | |
| power factor | — |